Heat energy is published as GJ while the meter uses kWh
The problem
Some Kamstrup heat meters report heat energy in kWh, while the Kamst-IR Gateway currently publishes this value in Home Assistant as GJ.
The gateway does read the raw value from the meter correctly. The issue is only with the unit published through MQTT autodiscovery. Most meters provide the heat energy value in GJ, while a limited number use kWh. For this reason, we chose to provide the value in GJ through MQTT autodiscovery.
Example
A Kamstrup MULTICAL 403 may report a value of:
22,719.8 kWh
The gateway currently publishes this as:
22,719.8 GJ
Home Assistant can then interpret this as approximately 6.3 million kWh.
Solution: create a custom sensor in Home Assistant
You can easily work around this by creating a template sensor in Home Assistant that takes the value from the existing sensor and defines it as kWh.
No conversion factor is required. The gateway already reads the value from the meter correctly; only the published unit is incorrect.
Add the following YAML:
template:
- sensor:
- name: "Heat Energy Kamstrup"
state: "{{ states('sensor.smart_gateways_kamst_ir_f879b0_heat_energy') | float }}"
unit_of_measurement: "kWh"
device_class: energy
state_class: total_increasing
availability: "{{ has_value('sensor.smart_gateways_kamst_ir_f879b0_heat_energy') }}"Note: the exact name of the existing sensor may differ between installations. In the YAML, use the entity ID of your Kamst-IR heat energy sensor. This consists of the last 6 characters of the gateway’s MAC address.
After adding the template sensor, you can use this new sensor in the Home Assistant Energy Dashboard.
First check the unit used by your meter
Not every Kamstrup meter reports heat energy in kWh. Many of the meters we encounter use GJ.
Therefore, first check which unit your meter actually uses.
- Meter reports kWh β use the template sensor above
- Meter reports GJ β the standard sensor can be used
Only use the template when the meter itself reports the energy value in kWh.
Note: the power value may also have an incorrect unit
Some Kamstrup meters report the current heat power in kW.
The Kamst-IR Gateway currently publishes this value as W. As a result, the displayed power can be a factor of 1,000 too low.
Example
A meter may report approximately:
4.15 kW
The gateway may currently publish this as:
4.15 W
In other words, an actual heat output of approximately 4,150 W would be displayed as only 4.15 W.
This does not affect the measured energy total; it only affects the displayed power value.